Free UK Delivery

TRIDONIC PC1X35-6 Emergency lighting units PC COMBO, PC T5 COMBO lp, 220 – 240 V 50/60 Hz Linear fluorescent lamps

TRIDONIC PC1X35-6 Emergency lighting units PC COMBO, PC T5 COMBO lp, 220 – 240 V 50/60 Hz Linear fluorescent lamps
SKU: PC1X35-6
Excl. VAT: £37.95 Incl. VAT: £45.54
Tridonic

Product Description

Details

TRIDONIC PC1X35-6 Emergency lighting units PC COMBO, PC T5 COMBO lp, 220 – 240 V 50/60 Hz Linear fluorescent lamps

  • Combination of electronic ballast and emergency lighting unit
  • For T5 fluorescent lamps
  • Low profile casing (21 x 30 mm cross-section)
  • For manual testing of the emergency lighting function
  • 5-year guarantee
  • Lightweight one-part emergency lighting unit
  • Simple wiring
  • No compatibility problems
  • 1 or 3 h rated duration
  • Selectable operating time (jumper)
  • Lamp warm start in normal operation
  • Cathode heating in emergency mode
  • AC operation of all lamps
  • Automatic restart after relamping in normal operation
  • Green charge status display LED
  • Intelligent Voltage Guard (overvoltage indication and undervoltage shutdown)
  • Optional test switch
  • Checking the emergency lighting function by interrupting the unswitched phase
  • IDC (insulation displacement connection)
  • Electronically controlled battery charging
  • Deep discharge protection
  • Short-circuit-proof battery connection
  • Polarity reversal protection for battery
  • High-temperature cells
  • NiCd or NiMH batteries
  • D, Cs or LA cells
  • Blade terminals for simple connection
  • 4-year design life
  • 1-year guarantee
  • For battery compatibility refer to datasheet
Rated supply voltage 220 – 240 V
Mains frequency 50 / 60 Hz
Mains voltage changeover threshold According to EN 60598-2-22
Start time ~ 1.6 s
tc point max. 70 °C
tc point (PC 2x54-6 T5 COMBO lp) 75 °C
Ambient temperature ta 0 ... +55 °C
Operating frequency (normal operation) 40 – 50 kHz
Operating frequency (emergency mode) 20 – 30 kHz
Overvoltage protection 320 V (for 1 h)
Battery charging time 24 h
Charge current 1 h 105 mA
Charge current 3 h 210 mA
Leakage current (PE) < 0.5 mA